MLSS Analyzer |
|
 |
 |
Outline |
| |
The MLSS Analyzer(DWA-3000A-MLSS) has built-in microprocessor, equipped the best function and specification for measuring MLSS in the industry.
It is designed to analyze Mixed Liquid Suspended Solids(MLSS)¡¯ concentration values wherever and any condition as quickly and accurately on the live. And It is used to measure Sludge¡¯s high concentration in various places such as sewage disposal plant, livestock and excrement treatment plant, industrial waste water, and water disposal industry, and etc.
This compact case has built-in backlight graphical LCD, manual/auto calibration, Relay contact output(5 contacts), trend analysis function, and RS-232 , RS485 Communication function.
|
|
|
| |
 |
Function / Features |
| |
- Certificate : New Excellent Product (NeP)
- Certificate : Certificate of Patent
- Certificate : Certificate of CE
- English Display
- Real Time Trend Graph Function
- Relay Contact output - HH, L, L, LL & Cleaning Contact
- Simple Operation by 7 Keypad Button
- Large Size LCD Screen (160*128)
- Back-Light LCD
- Isolated(4~20, 0~20, 0~24 mA DC) Output Transmission
- RS-232(Std.), RS485(option) Communication
- Automatic Cleaning Control(Air jet, Water jet) Function
- Wall Mounting
- Microprocessor-based Digital Program Controller |
| |
|
 |
Specifications |
| |
- Code No. : 413130001MLSS
- Model : DWA-3000A-MLSS
- Channel : Single channel
- Range : 0 ~ 15,000 mg/L (Resolution: 1)
- Measuring Method : IR LED 880nm Transmitted
- Power : AC 110/220V, 50/60Hz, 3VA
- Accuracy : ¡¾ 3% of F.S
- Repetition & Reappearance : ¡¾ 3% of F.S
- Response time : 30 sec(90% saturation)
- Analog output : 4~20mA DC(STD.)
- Digital output : RS-232C(std.), RS485(option)
- Relay output : HH, H, L, LL & Cleaning Contact
- Display : Trend graph, measuring value
- Humidity : max. 90%(non-condensing)
- IP Rating : IP65
- Size : 240(W)x180(H)x115(D)
- Installation : Wall mounting |
|
| |
MLSS Analyzer |
|
 |
 |
Outline |
| |
The MLSS Analyzer(DWA-3000B-MLSS) has built-in microprocessor, equipped the best function and specification for measuring MLSS in the industry.
It is designed to analyze Mixed Liquid Suspended Solids(MLSS)¡¯ concentration values wherever and any condition as quickly and accurately on the live. And It is used to measure Sludge¡¯s high concentration in various places such as sewage disposal plant, livestock and excrement treatment plant, industrial waste water, and water disposal industry, and etc.
This compact case has built-in backlight graphical LCD, manual/auto calibration, Relay contact output(3 contacts), trend analysis function, and RS-232 Communication function.
|
|
|
| |
 |
Function / Features |
| |
- Certificate : New Excellent Product (NeP)
- Certificate : Certificate of Patent
- Certificate : Certificate of CE
- English Display
- Real Time Trend Graph Function
- Relay Contact output (3 contacts)
High, Low Alarm & Cleaning Contact
- Simple Operation by 7 Keypad Button
- Large Size LCD Screen (160*128)
- Back-Light LCD
- Isolated(4~20, 0~20, 0~24 mA DC) Output Transmission
- RS-232 Communication
- Automatic Cleaning Control(Air jet, Water jet) Function
- Panel mounting (DIN 144 size)
- Microprocessor-based Digital Program Controller |
| |
|
 |
Specifications |
| |
- Code No. : 413130002MLSS
- Model : DWA-3000B-MLSS
- Channel : Single channel
- Range : 0 ~ 15,000 mg/L (Resolution: 1)
- Measuring Method : IR LED 880nm Transmitted
- Power : AC 110/220V, 50/60Hz, 3VA
- Accuracy : ¡¾ 3 % of F.S
- Repetition & Reappearance : ¡¾ 3 % of F.S
- Response time : 30 sec(90% saturation)
- Analog output : 4~20mA DC(STD.)
- Digital output : RS-232C
- Relay output : High, Low & Cleaning Contact
- Display : Trend graph, measuring value
- Humidity : max. 90%(non-condensing)
- IP Rating : IP65
- Size : 155(W)x155(H)x184(D)
- Installation : Panel mounting (DIN144 Size) |
|
| |
MLSS Controller |
|
 |
 |
Outline |
| |
The MLSS Controller(DWA-2000A-MLSS) has built-in micro processor and DIN96 Standard size for install on-the-spot. It is simple and rapid indication controller to measure MLSS values constantly, and it is used to measure
MLSS concentration and Sludge¡¯s high concentration in various places such as sewage disposal plant, livestock and excrement treatment plant, industrial waste water, and water disposal industry, and etc.
This compact case has the built-in high brightness 7-Segment, manual/auto calibration, Relay contact output(3 contacts), and this product actualizes LOW-COST to make the customer¡¯s satisfaction and faith. |
|
|
| |
 |
Function / Features |
| |
- Certificate : Certificate of Patent
- Certificate : Certificate of CE
- Relay Contact output (3 contacts)
High, Low Alarm & Cleaning Contact
- Simple Operation by 4 Keypad Button
- High brightness 7-segment display
- Isolated(4~20, 0~20, 0~24 mA DC) Output Transmission
- Automatic Cleaning Control(Air jet, Water jet) Function
- Panel mounting (DIN 96 size)
- Microprocessor-based Digital Program Controller
- Low-Cost for user satisfaction |
| |
|
 |
Specifications |
| |
- Code No. : 413120001MLSS
- Model : DWA-2000A-MLSS
- Channel : Single channel
- Range : 0 ~ 15,000 (Resolution: 1)
- Measuring Method : IR LED 880nm Transmitted
- Power : AC 110/220V, 50/60Hz, 3VA
- Accuracy : ¡¾ 3 % of F.S
- Repetition & Reappearance : ¡¾ 3 % of F.S
- Response time : 30 sec(90% saturation)
- Analog output : 4~20mA DC(STD.)
- Relay output : High, Low & Cleaning Contact
- Display : measuring value, Temp (7-segment)
- Humidity : max. 90%(non-condensing)
- IP Rating : IP54
- Size : 96(W)x96(H)x125(D)
- Installation : Panel mounting (DIN96 Size) |
|
| |
|
|